Question:
If I only need air-conditioning,
what kind of model would you suggest? Will
I still require the heat
pump?
Answer:
If A/C is its only function, an HC model (heat
only) will perform perfectly, but it must be
ordered as an A/C only unit. Otherwise it
will be labelled as a "Heat Only" unit. The
plumbing is the same in the cabinet, but the
labels will be wrong if it is not specified. A
Manual J heat gain calculation is still required
on the building to determine which size unit
will perform properly.
Question:
What is the COP for the EarthLinked system at various outside temperatures and for various applications?
Answer:
Our Geothermal system boasts verified coefficients of performance (COPs) from 3.5 to greater than 5 in space heating and cooling. For a complete overview of the system's performance under various conditions, have a look at our complete performance table.
Question:
Can you describe the Active Charge
Control (ACC) and its
function?
Answer:
The ACC is a patented EarthLinked system
component that has three functions:
- allows only saturated refrigerant vapour and
entrained oil to be returned to the compressor,
which maximizes compressor and system
performance and extends compressor life;
- is a reservoir for holding liquid
refrigerant and oil that is not needed in
circulation at any given time, thereby modulates
to allow the system to operate at maximum
efficiency throughout the full range of
operating conditions; and
- is equipped with sight glasses (windows) to
enable quick and accurate refrigerant charging
of the system.
Click
here for a detailed description of the ACC.
Question:
The diagram for the EarthLinked
water heater application seems to require both
your system and a separate water heater. Why do
you need both a storage tank and water heater?
Please explain the radiant floor and house
supply hot water. Is the supplemental water
heater needed because the recovery time of your
geothermal system is too slow?
Answer:
Heating hydronic water or domestic water
are two processes. First, domestic: typically
domestic hot water (DHW) is heated to about
140°F for dishwashing and to assure hot water.
The hot water is tempered with cold water at its
outlet to make it bearable for bathing. The
EarthLinked system can very efficiently heat DHW
to 120° F, then supplemental heat is used to
"top off" the remaining 20°F.
Consider the following example: people are
familiar with their shower control handle. For
years, they knew that the 12 o'clock position
will yield water at the desired temperature (hot
and cold mixing), and they have always had
enough hot water to finish showering. After
installing the EarthLinked geothermal water
heating system, their water is heated three
times faster for 1/3 the cost. The first night
in the shower, they notice that the shower
control must now be set for 10 o'clock position
to deliver the usual water temperature. No
problem--new set point. Later, the water begins
to get cold before the shower is over. Why?
Because the water in the tank is not 140°F
anymore. It is 120°F. So, more of it is required
(and less cold water) to maintain the same
outlet temperature. So, the heated water is used
faster--and drained completely. The heat pump is
attempting to replace the water, but even a
4-ton unit can heat only two gallons 50 F per
minute. 1 BTU = 1 lb water x 1 degree F. One
gallon of water weighs 8.34 lbs.
Yes, the EarthLinked heats water faster and
cheaper, but even the largest system would
struggle to keep up with a normal shower's usage
rate. Why not make the tank bigger so you do not
run out? Because an EarthLinked system
prioritizes DHW. If it diverts to heat DHW, its
main load (heated air or hydronic heating) must
pause and wait while the DHW tank is satisfied.
Discomfort may be felt in the main house while
you wait for the DHW to finish. The system heats
only one thing at a time. This is why we
recommend two 40 gallon tanks. It is the best of
both worlds.
The pre-heat tank is serviced by the
EarthLinked and heated to 120°F. The main tank,
plumbed and wired normally draws the pre-heated
water into itself and tops it off to 140°F.
EarthLinked heated water from 50°F to 120°F,
then electrically heated water from 120°F to
140°F. You get the benefit of the EarthLinked
heating the water up to 120°F and the hotter
water from the main tank (140°F) to which you
are accustomed. Next, two smaller 40 gallon
tanks can be used which are cheap and readily
available. Lastly, if the EarthLinked has minor
trouble, you have the back-up of the main tank
which can heat from 50°F to 140°F by itself.
Hydronic Water Heating (HWH) It is best to
design the in-floor heat exchanger to operate at
about 115°F. The water is hot enough and little
stress is placed on the compressor or other
parts. One single 40 gallon water tank is
adequate per system. The water tank serves only
as a small buffer between heat pump and
flooring. The system will satisfy the tank
thermostat fairly quickly (no load). When the
floor loads come on, the tank will be drained of
its heat rapidly. The heat pump will likely not
be able to keep up with the drainage rate, but
it will then begin to supply heat at its own
rate adequate to change the temperature of the
floor and eventually satisfy the load and the
thermostat settings. Once the in-floor pumps
stop, the heat pump need only finish heating the
water in the tank to the set-point.
Question:
How do you get the
refrigerant gas into a liquid state before
entering the earth loops?
Answer:
In the air conditioning mode, the hot gas
enters the ground loop directly after it leaves
the compressor. Then it condenses into a
liquid before it leaves the earth loops.
Question:
Are auxiliary pumps
used to circulate refrigerant?
Answer:
The only "pump" that circulates the
refrigerant is the compressor itself.
There are no other refrigerant pumps involved.
One circulates water to/from the water tank in
the water heating mode.
Question:
What is the highest
sustained room temperature in the heating mode
and lowest cooling temperature in the cooling
mode?
Answer:
Sustaining temperatures far outside the comfort
range is a unique situation but is possible
within reason. The limiting factor is the
pressures of the refrigerant at those extremes,
because the pressures of the refrigerant are
directly proportional to the temperatures of the
refrigerant, and the temperature of the air over
the indoor coil dictates the temperature of the
refrigerant.
I can hypothetically determine the
temperature extremes, though these air
temperatures have not been tested or proven as
far as their limits go. Expect the highest
indoor temperature to be sustained between 100°F
and 110°F. Expect the lowest indoor temperature
to be sustained between 50°F and 60°F.
Temperatures below this begin to drift into the
Medium Temperature Range. These temperatures
are used for refrigeration, and, while the
EarthLinked could continue to drop the
temperature lower, it would require a method of
defrosting the indoor coil, because it would be
operating below freezing (32°F).
ECR's controls are currently operating
refrigeration equipment used for chilling milk
and commercial refrigerators, but these
applications are design-sensitive, and the
installers are aware of the operating criteria
when they purchase the controls. If air
temperatures are required above or below these
indicated, ECR may be able to assist in
designing such equipment utilizing our patented
refrigerant controls.
Question:
Why does ECR specify
the use of the Danfoss HP8000 thermostat with
its heat pumps? Other than it being
programmable, does it work differently than
typical heat pump thermostats? What will
happen if I use a different make and
model?
Answer:
The Danfoss thermostat line was chosen
because of a relatively unique function it
performs. It is able to identify the
"Balance Point" automatically with no external
sensors or human input. The Balance Point is the
temperature outside where a building's heating
system, such as a furnace or heat pump, can no
longer provide the heat at the
same rate at which the building is
losing heat. So, for every degree below the
Balance Point, the indoor temperature will drop
an equal number of degrees even though the
heating system is operating continuously.
Obviously, supplemental heat (back up) is
required below the Balance Point--enough heat to
provide for the building's heat loss down to the
lowest outdoor temperature expected.
All heat pumps are designed to provide heat
for the building, but none are expected to
provide all of the heat down to the lowest
outdoor temperatures. All heat pumps
require supplemental heat sources. Typical heat
pump thermostats have two heat stages. The
first bulb operates the heat pump. If the
heat pump can no longer supply all of the heat,
the indoor temperature drops two degrees
activating the second stage (supplemental heat
source). As the second stage switch
toggles the supplemental heat, the heat pump
operates continuously via the first stage
switch. This method of operation is
adequate for air-source heat pumps because the
outdoor air temperature (heat source) is
relatively constant.
Ground source heat pumps should not operate
continuously. Doing so causes the earth
temperature (heat source) to be reduced over
time. The recovery time for the earth
requires more time than that of the outdoor air,
and, as the heat source is reduced, the system's
capacity is also reduced. Prolonged
periods of operation in this fashion can "strip"
the heat from the earth rendering the ground
source heat pump inadequate if not
disabled. Once this occurs, the heat pump
can not supply enough heat to satisfy the
thermostat even if the outdoor temperature is
greater than the Balance Point.
The Danfoss HP8000 thermostat utilizes an
internal microprocessor which contains an
algorithm that recognizes the Balance
Point. When the thermostat calls for
heating, the heat pump always responds
first. While the heat pump operates, the
thermostat constantly monitors the rate at which
the indoor air temperature is rising in an
attempt to reach the set-point. If the
indoor air temperature is not rising at a rate
of seven degrees F. per hour, the thermostat
turns on the supplemental heat to operate with
the heat pump. Thereafter, the
supplemental heat remains on with the heat pump
until the set-point is achieved.
Then, the thermostat turns off both the
heat pump and the supplemental heat. The
heat pump is allowed to rest momentarily, the
ground is not stripped of its heat, and the
earth temperature remains high enough to control
indoor temperature when the outdoor temperature
is greater than the balance point.
If an alternative to the HP8000 thermostat is
used instead, an additional outdoor thermostat
must be used in order to recognize the balance
point. A heat loss/gain calculation will
yield a numerical value for the balance
point. The outdoor thermostat must be
manually adjusted to equal this value, then
installed, and wired. ECR will provide
wiring instructions to make the "other"
thermostats operate the EarthLinked system
correctly. This control method will yield
a virtual replication of the HP8000's method
saving the earth from having its temperature
stripped, but reduced levels of comfort and
controllability will be noticeable.
All alternative thermostats require the outdoor
thermostat to operate the EarthLinked system
properly.
Question:
Why is it economic
to use supplemental heat to "top off" the water
temperature?
Answer:
The EarthLinked system is capable of heating the
water from its supply inlet temperatures
(typically 50°F to 75°F up to 120°F) three times
faster and at one quarter the cost of standard
electric heating. When a compressor is called
upon to deliver heat to water that is hotter
than 120°F, there is greater resistance to heat
transfer, so the compressor must work harder and
use more electric energy. Although it may still
be twice as efficient as standard resistance
heating elements, it is necessary to avoid
overloading the compressor. The remaining
temperature rise is accomplished with
supplemental heat, usually electric heating
elements. Thus the EarthLinked system does most
of the heating (69-77%) with high efficiency and
the remainder is done with supplemental
heat.
Question:
Is a two-speed
compressor feasible with an EarthLinked
system?
Answer:
The velocity of the refrigerant that circulates
for heat exchange in the earth loops is crucial
because it must maintain a sufficient rate of
circulation to continuously transport the
compressor lubricating oil. A two-speed
compressor would reduce the velocity to the
extent that oil would not be returned to the
compressor, which would be detrimental to the
unit.
